The Control
Panel
Isolcell introduces innovative technologies developed specifically for oxygen-reduction systems
Control indicating equipment (CIE) N2 ORS®
The heart of the system
The N2 ORS® CIE control panel manages the entire installation. It handles samples from the virtual grid andactivates and/or deactivates the integrated and interfaced equipment according to programmed response plans. It also manages control systems preventing an unintended low-oxygen atmosphere in adjacent areas, as well as shutdown procedures when preset oxygen thresholds are reached and alarms when necessary.
Because the control panel is critical to oxygen-depletion fire prevention, specific standards require self-diagnostics, redundancy and a dual power supply to keep the installation operating for at least 24 hours if the main power supply fails.
Oxygen sensor
N2 ORS®
Oxygen analysis for small and large spaces
Oxygen concentration in the protected area is measured according to the applicable standards through Isolcell’s variable-pitch virtual grid N2 ORS®. The arrangement ensures that failure of one measuring element does not affect the overall measurement. The more recent ISO 20338:2019 standard, unlike EN 16750:2017 in this respect, specifies that each detector must measure oxygen continuously, at least once a minute, and that response times must be documented. The whole system remains operational as long as at least one sensor, or 20% of the sensors, remains operational.
Because the control panel is critical to oxygen-depletion fire prevention, specific standards require self-diagnostics, redundancy and a dual power supply to keep the installation operating for at least 24 hours if the main power supply fails.
Our oxygen sensor
is VdS certified. / Cert. Nr. G 222058

Advanced technology
for new goals
The N2ORS® oxygen sensor contains three individual sensorswith mutual measurement diagnostics and a triple-redundant majority architecture. Readings are processed using 2oo3 voting logic (2 out of 3 components), providing one accurate and unambiguous value and ensuring a high level of safety, as shown by the certification of our oxygen sensors under IEC 61508:2010 at SIL-3 level.
The control panel
Power supply and electrical system
In the N2 ORS® system, equipment (panel, sensors, generators, valves, warning devices and so on) interoperates by exchanging protocol-based data. During design, this requires particular attention to transmission parametersto prevent reflections, interference and random faults. The system uses dual connections in closed loops. Cable paths are separated so that damage is likely to affect only one branch of a loop; a fault in one branch will not compromise the other.
The power supply also uses a dual loop connection, operating on the same principle as data transmission. The power supply has two sources: a primary sourcefrom the public grid and a backup sourcecomprising batteries and power units. If the primary source fails, the backup automatically takes over. When primary power returns, it automatically replaces the backup.

System synoptic display
Remote oxygen-
reduction system
The synoptic display works over the web via an IP address and presents control-panel data in an intuitive graphic format. The installation’s operating conditions (normal, fault, alarm and so on) and corresponding switching operations are logged and saved for later viewing. The display allows users to:
- view events from the control panel
- check that the entire system works properly
- view notifications and alarms
- inspect operating modes